Module working pressure, MPa, (kgs/sm2); 6,4 (65)
Module trial pressure, MPa, (kgs/sm2); 9,8 (100)
Start pressure pneumatic , MPa, (kgs/sm2);
• minimum;1,5 (15)
• maximum;6,4 (65)
Actuation pressure of diaphragm safety device, MPa, (kgs/sm2);
• minimum;7,4 (75)
• maximum;8,2 (83)
Number of module actuation per lifetime, once;10
Exit time GOTV 95% by weight, s, no more;10
Remainder GOTV in a balloon, kg, no more;0,6
Module life before decommissioning, year, at least;25
Ambient temperature during module operation;from -20°С before +50°С